Cornell University Ergonomics Web

DEA3500: Ambient Environment: Zonal Cavity

BASIC DATA

Example: Designing lighting for a laboratory

Reflectances -

Room dimensions -

Working plane - work tables are 3.0 feet above floor

Room is air-conditioned and kept very clean (clean conditions needed for experiments).

Total space including fully recessed luminaires (ceiling) and walls, is cleaned every 19 months.

Lamps are replaced as soon as they burn out. Max. distance between lamp rows center to center = 8'.

Desired lighting level = 100 footcandles

Planning to use 30 luminaires in five continuous rows to provide uniform illumination.

CALCULATING THE COEFFICIENT OF UTILIZATION LUMINAIRES ETC.

Zonal Cavity Coefficient of Utilization Calculation

Room length = 30', breadth = 20', hrc = 7.0', hfc = 3.0'

Steps:

  1. Room cavity ratio = 2.9; ceiling cavity ratio = 0.0 (recessed lamps); floor cavity ratio = 1.2 (i.e. for 20 x 30 x 3' depth)

  2. Effective ceiling reflectance = .80; effective floor reflectance = .20 (on table for cavity ratio 1.2, % floor reflectance = 30, % wall below work plane = 10%

  3. Coefficient of Utilization for this luminaire = .48 (graph - reflectances, room cavity ratio 3). No correction required here.

  4. Calculate footcandles. Planning to use 30 luminaires and 2 lamps per luminaire. Check predicted footcandles against recommended levels in table. Alternatively for 100 fc calculate number of luminaires. # luminaires = 100 fc x 600(area = 60,000 = 25 luminaires (5 less than initial 2 x 3150 x .48w x .78 LLF 2358.7 design.

VCP from table VCP crosswise = 71 VCP lengthwise = 70

CALCULATING THE LIGHT LOSS FACTOR

Calculations

1. Energy requirements

To maintain 100 footcandles lighting level, how much energy needs to be used?

On graph:

Calculate spacing and fill in fact sheet:

2. Calculate light loss factor.

Use sheet provided. Steps:

Calculate light loss factor: LLF = 1.0 x .98 x 1.0 x .88 x .90 = .78

CALCULATING VISUAL COMFORT PROBABILITY

Visual Comfort and Glare

Visual Comfort Probability (VCP)

VCP rating = % people who, if seated in the most undesirable location, will find the lighting acceptable. Computation of VCP is complex, but tables can be used for approximating VCP. Tables assumes 80% effective ceiling reflectance, 50% wall reflectance, 20% effective floor cavity reflectance.

Work surface illumination = 100 fc.

Luminaire mounting heights 8.5, 10, 13, or 16'

Uniform luminaire distribution through space.

Rooms of stated lengths and widths.

Observed seated with eye height 4' and 4' from rear wall.

Observer looking directly forward.

Observer field of view limited to 53o angle above and directly forward.

When VCP 70 or more for both lengthwise and crosswise views, then glare should not be a problem and most people should be comfortable.


Go to the next lecture